YBM series of prefabricated substation (European style)
YBM, YBP series of prefabricated substation is the combination of the HV electrical apparatus, transformer, and low voltage transformer equipments and therefore is used in the high-rise buildings, residential districts, urban and rural construction, hi-tech development zone, small and medium size enterprise, mine and oil fields and the temporary construction sites to receive and distribute the power.
YBM, YBP series of prefabricated substation is complete set, small sized, compacted structure, running safely, easy maintenance, and mobile. And it only takes the 1/10-1/5 of the space of the same capacity of civil construction distribution, and therefore greatly reduces the construction cost. It can be used in the ring net distribution system, double power distribution system or radiator terminal distribution system. It is the new complete set equipment used for rural and urban substation construction and reformation.
YBM, YBP series of prefabricated substation is fully in accordance with the standard of SD320-1992 (the technology of Boxes substation) and the standard of GB/T 17467-1998 (HV/LV prefabricated substation). The shell is made of non-metal, composite board or the steel sheet as per the users.
YBM substion main technical parameters:
Capacity: 50~4000KVA
Votage: 11/0.4KV, 13.8/0.4kv,20kv/0.4
HV switchgear: Vacuum type panel (630~3150A)/ SF6 panel(630A)
Transformer: S11 11/0.4KV 50~4000KVA
LV switchgear:630A~6300A
Technical parameters
Unit |
Item |
HV electrical apparatus |
Transformer |
LV electrical apparatus |
Rated voltage Ue |
KV |
7.2、12 |
6/0.4、10/0.4 |
0.4 |
Rated capacity Se |
KVA |
|
P: 200~1250 |
|
M: 50~400 |
||||
Rated current le |
A |
200~630 |
|
100~3000 |
Rated drop-out current |
A |
Load switch400~630A |
|
15~63 |
KA |
Composite apparatus |
|||
Rated short time withstand current (S) |
KA(xs) |
20*(2) |
200~400KVA |
15*1 |
12.5*(4) |
400KVA |
30*1 |
||
Rated withstand current (peak) |
KA |
31.5、50 |
200~400KVA |
30 |
400KVA |
63 |
|||
Rated making current |
KA |
31.5、50 |
|
|
Power frequency withstand voltage 1min |
KA |
Phase-earth and phase-phase 32、40 |
Oil-immersed:35/5min |
≤300V:2KV |
34、48 |
Dry-type:28/5min |
300、600V:2.5KV |
||
Lightning impulse |
KV |
Phase-earth and phase-phase 60、75 |
75 |
|
Isolation fracture:75、85 |
75 |
|||
Noise level |
dB |
|
Oil-immersed:55 |
|
Dry-type:65 |
||||
Protection degree |
|
|
IP23D |
|
External dimension |
as per the capacity of the transformer |